Eclipse Combustion 6500 Manual do Utilizador Página 33

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 32
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
33
Yearly Checklist
1. Test (leak test) safety shut-off valves for tightness of closure.
2. Test pressure switch settings by checking switch movements against pressure
setting and comparing with actual impulse pressure.
3. Visually check ignition cable and connectors.
4. Make sure that the following components are not damaged or distorted:
• the burner nozzle
• the spark plugs
• the flame sensors
• the flame tube or combustion block of the burner
Vista de página 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 45 46

Comentários a estes Manuais

Sem comentários