Bi-Flame Version 1.8 Model 6500No. 826, 05/03Instruction ManualDual Burner Monitoring System

Página 2 - LIABILITY AND

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0310In this section, you will find descriptions of the various moduleswhich comprise the Bi-Flame du

Página 3 - About this manual

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0311Sensor ModuleThe sensor module is the flame sensing module of the Bi-Flame. It ismounted in the

Página 4 - Table of Contents

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0312INTRODUCTION This section details the location, selection and description of theBi-Flame DIP swi

Página 5

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0313S2 DIP SwitchesThe S2 DIP switches permit programming of timing and sequencefunctions of the Bi-

Página 6

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0314INTRODUCTION This section describes the function features of the Bi-Flame that canbe found on th

Página 7 - Introduction

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0315Recycle ModeWhen selected, the Bi-Flame will restart the sequence after flame orair failure. The

Página 8 - Specifications

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0316Auxiliary InputsThis feature provides four auxiliary inputs which are monitored bythe Bi-Flame a

Página 9 - DIMENSIONS

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0317History Log (continued)4) Release the ENTER key and the most recent lockout messagewill display

Página 10 - Modules Description

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0318Valve Leak Sensing Device (VLSD) InterfaceThe Bi-Flame Valve Leak Sensing Device (VLSD or VDK) i

Página 11 - Remote Display

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0319Remote Display UnitThe remote display with keypad allows remote reset and activationof the histo

Página 12 - DIP Switch Selection

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/032Copyright 2003 by Eclipse Combustion. All rights reservedworldwide. This publication is protecte

Página 13 - DIP SWITCH SETTINGS

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0320AirThis LED illuminates when the air switch is closed and power isthereby applied to the air swi

Página 14 - Function Summary

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0321System FaultsA system fault (illuminated by the fault LED on the logic cards) pre-vents gas igni

Página 15

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0322In this section, the necessary procedures are detailed to integrate aBi-Flame into a burner syst

Página 16

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0323Route ignition wiring a sufficient distance from all sensors and otherlow voltage wiring to avoi

Página 17

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0324When installed, the remote display must be grounded. Panelmounting is through a 1/4 DIN cutout (

Página 18

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0325Figure 6.1 Terminal Strips Identification & LocationMain ChassisJ1J2J3J4J5J6J7RemoteDisplay

Página 19

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0326Figure 6.2 Wiring Diagram & Connections–Main ChassisOn/OffAlarmFan MotorInterlocks & Li

Página 20

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0327This section describes the proper wiring, installation and sighting con-siderations for all sens

Página 21

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0328Flame rods should be used only on gas burners. They accumulatesoot on oil burners, causing nuisa

Página 22 - System Installation

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0329Aim scanners at the third of the flame closest to the burner nozzle, asshown at left. This is es

Página 23

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/033AUDIENCEIMPORTANT NOTICESAbout this manualThis manual has been written for the people who select

Página 24 - REMOTE RESET

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0330INTRODUCTIONThis section describes the test procedures that must be performedafter installation

Página 25 - Figure 6.1

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03311) Manually shut off the fuel supply to one individual pilot andmain burner, or all burners if t

Página 26 - Figure 6.2

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0332INTRODUCTION This section is divided into two parts:• The first part describes the maintenance p

Página 27 - Sensor Installation

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0333Yearly Checklist1. Test (leak test) safety shut-off valves for tightness of closure.2. Test pres

Página 28 - SCANNERS

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0334TROUBLESHOOTINGPROBLEM POSSIBLE CAUSE SOLUTION• Main valve is not closed.• Air pressure switch h

Página 29 - SCANNER SIGHTING

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0335INTRODUCTION This section covers how the optional remote display is used withthe Bi-Flame. The r

Página 30 - Test Procedures

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0336Table 10.1 Bi-Flame Operating SequencePOWER ONWas internal safe start check successful?EXTERNAL

Página 31 - LIMITS AND INTERLOCK

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0337Table 10.1 Bi-Flame Operating Sequence (continued)BURNER START-UPIs voltage present at air flow

Página 32 - Troubleshooting

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0338Table 10.1 Bi-Flame Operating Sequence (continued)BURNER START-UP (continued)Is flame signal pr

Página 33

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0339Table 10.1 Bi-Flame Operating Sequence (continued)BURNER SHUTDOWNShutdown is started by opening

Página 34 - TROUBLESHOOTING

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/034About this manual...3Table of co

Página 35 - Messages

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0340MESSAGE TYPE EXPLANATIONTable 10.2 Remote Display Diagnostic Messages (Listed Alphabetically)Lo

Página 36 - BURNER START-UP

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0341Table 10.2 Remote Display Diagnostic Messages (continued)MESSAGE TYPE EXPLANATIONLockout Main

Página 37

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0342Table 10.2 Remote Display Diagnostic Messages (continued)MESSAGE TYPE EXPLANATIONHold Flame si

Página 38 - BURNER START-UP (continued)

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0343AppendixCONVERSIONFACTORSMetric to English.FROM TO MULTIPLY BYcubic meter (m3) cubic foot (ft3)

Página 39 - BURNER SHUTDOWN

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0344ILLUSTRATED PARTSLIST12 3 476View shown with cover removed.Pos.No.Qty. DescriptionEclipsePart Nu

Página 40 - Table 10.2

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/0345

Página 41

826 Instruction Manual 05/03

Página 42

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/035Function Summary...14Introduction.

Página 43 - Appendix

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/036Sensor Installation ...27Introduc

Página 44 - ILLUSTRATED PARTS

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/037The Eclipse Combustion Bi-Flame Burner Monitoring Systemcontrols the start-up sequence and monito

Página 45

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/038INTRODUCTIONSpecificationsThis section gives a detailed overview of Bi-Flame specifications anddi

Página 46 - 826 Instruction Manual 05/03

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/039DIMENSIONSMountingHoles (4)5 mm(3/16") Dia.237 mm(9-5/16")270 mm(10-5/8")229 mm(9&